You cool a 50kW GPU rack with air by designing the building around airflow instead of refrigeration. IDACORE Depot 01 in Northeast Washington does this today. It uses cross-flow free-air cooling through MERV 13 filters, a direct evaporative wet wall for summer, and no compressors or chillers. The design-target PUE is about 1.1–1.2, and it's live now.
Can Air Move 50kW Out of a Single Rack?
Yes. You have to stop thinking about the room and start thinking about the air path.
Every watt a GPU server draws becomes heat, and air carries that heat away according to a simple relationship. In imperial units at roughly sea-level density:
CFM = (Watts × 3.412) / (1.08 × ΔT°F)
≈ 3.16 × Watts / ΔT°F
ΔT is the temperature rise from server inlet to server exhaust. Here's what a 50kW rack needs at different rises:
| Inlet-to-exhaust ΔT | Airflow required for 50kW |
|---|---|
| 15°F | ~10,500 CFM |
| 20°F | ~7,900 CFM |
| 25°F | ~6,300 CFM |
| 30°F | ~5,300 CFM |
| 35°F | ~4,500 CFM |
So you're moving somewhere between 5,000 and 8,000 CFM through one cabinet. That's a lot of air. It isn't exotic.
The servers' own fans do the work of pulling air through the chassis. The building has three jobs:
- Deliver that volume to the front of the rack.
- Deliver it at a temperature the hardware accepts.
- Get the exhaust out before it wraps back around to the inlets.
That last job is where legacy rooms fall apart. A raised-floor room built for 5–10kW racks pushes cold air through perforated tiles, and each tile delivers a few hundred CFM. Put a 50kW rack in that room and the servers starve. They pull hot exhaust over the top of the cabinet and back into their own intakes. The usual fix is to add more CRAH units and drop the supply temperature, which means burning more compressor energy to fight a geometry problem.
Sound familiar?
Fan power matters too. At this density, server fans are a meaningful slice of the load, and they count as IT load in PUE math. You don't want inlet air so warm that every fan runs pinned at 100%. You also don't need it artificially cold. The target is a steady inlet temperature inside the ASHRAE recommended envelope of 64.4–80.6°F.
How Does Cross-Flow Free-Air Cooling Work in a Depot?
A Depot doesn't have a "room" in the traditional sense. It has an air path.
The Depot standard is built from Compute Modules of roughly 500kW each, either containerized or housed in a simple steel building. Two modules make a ~1MW Depot. Each module is laid out so air moves in one direction:
- Outside air enters through automated louvers on the intake side.
- It passes through MERV 13 filtration.
- In summer, it crosses a direct evaporative wet wall.
- It moves across the servers, front to back.
- It exits on the far side.
There are no compressors, no chillers, no refrigerant circuits, and no cooling towers. The louvers, recirculation, and wet wall are fully automated. The equipment you'd normally maintain on a mechanical contract simply isn't there, and equipment that doesn't exist can't fail.
What Happens on the Hottest Day of Summer?
This is where people get skeptical, so here's the math. A direct evaporative wet wall cools air toward its wet-bulb temperature. Good media typically runs 80–90% effective:
Supply temp = Dry bulb − Effectiveness × (Dry bulb − Wet bulb)
Take a hot afternoon at 95°F dry bulb with a 63°F wet bulb, which is typical of dry inland summers in the Pacific Northwest interior. At 85% effectiveness:
95 − 0.85 × (95 − 63) = 95 − 27.2 = 67.8°F supply air
That lands well inside the ASHRAE recommended range, with zero compressor energy.
This is also why siting matters. Direct evaporative cooling works because the air is dry. Put the same design somewhere with muggy summers and a high wet-bulb, and the math stops working.
Evaporation does add moisture, so the controls stage the wet wall and blend air to hold supply conditions inside the envelope instead of running wide open.
On filtration: MERV 13 is the grade commonly recommended for fine particulate, including wildfire smoke. Ask any free-air operator what grade they run. If the answer is lower, keep asking questions.
What About Winter?
Winter is the easy season, with one catch: outside air can be too cold and too dry to send straight at hardware. The automated recirculation blends warm exhaust back into the intake stream. That holds inlet temperatures steady and avoids the thermal swings that stress components. Your GPUs heat their own supply air for free.
How Does This Compare to a Conventional Cooling Plant?
| Conventional compressor/chilled-water room (typical market) | IDACORE Depot cross-flow free-air | |
|---|---|---|
| Heat rejection | Chillers or DX compressors | Outside air + direct evaporative wet wall |
| Compressors / chillers | Yes | None |
| Summer strategy | Mechanical refrigeration | Evaporative wet wall |
| Winter strategy | Economizer if equipped, often still mechanical | Automated recirculation blending |
| Typical PUE | ~1.5 is common for older facilities | Design target ~1.1–1.2 |
| Per-rack density | Often 5–15kW before hot spots | Up to 50kW air-cooled |
What Does No Compressors Mean for PUE and Your Power Bill?
Let's put numbers on one 50kW rack running flat out for a 730-hour month:
- IT energy: 50kW × 730 hours = 36,500 kWh
- At PUE 1.15 (Depot design target range): 41,975 kWh total
- At PUE 1.5 (common for older compressor-cooled rooms): 54,750 kWh total
- Difference: 12,775 kWh per month, roughly 153,000 kWh per year, from one rack
Multiply that by your utility rate and the cooling choice stops being academic.
Here's why that matters at IDACORE specifically. Depot pricing is $175/kW/month NNN plus power at cost. The $175 covers space, cooling, and facility infrastructure on a 36-month term. Power bills on top as metered IT load × PUE at the utility rate, with no markup.
Because power passes straight through, cooling efficiency is your money, not ours. A provider that marks up power has no particular reason to care about PUE. We built the PUE out of the design and hand you the result.
For 50kW of capacity, that's $8,750/month NNN, plus power at cost. The 12- and 24-month terms carry a higher rate. There's no minimum deployment size. The deposit and first month are due at signing.
The electrical path is short, too. We deliver 415V from IDACORE's own transformer on a utility primary feed, which means fewer transformation steps between the utility and your PDU.
Why Build Many Small Depots Instead of One Giant Campus?
Big campuses have a speed problem. A 100MW site needs a substation, and substations take years. A Depot is 5MW or less, typically about 1MW of IT load, and it's sited where the utility already has power available.
That's how Depot 01 went from plan to energized, and it's why racks there are powered in under two weeks from signing. You don't need an interconnection study timeline or a "Q3 next year, probably."
What Does "Cattle, Not Pets" Mean for Uptime?
We scale out horizontally across many Depots instead of gold-plating one site. The platform is resilient as a whole, and you pay for the resilience your workload needs:
- Base tier: utility-fed, no UPS or generator. This is the lowest cost, and it's the right fit for inference fleets and GPU marketplace hosts whose software already routes around a node going dark.
- Add-ons: UPS + generator, or battery energy storage (BESS), available as an add-on.
- Spread out: split capacity across multiple Depots for site-level redundancy.
Depot 01 carries a 99.9% uptime SLA.
The next Depots are planned for the Treasure Valley and Eastern Oregon, connected back to our Boise interconnect hub over metro fiber.
What About the Network?
IP transit is delivered on-site from our own ASN, AS36824, with Lumen and Cogent upstreams. You get BGP, IPv4/IPv6, and 1G, 10G, or 100G handoffs, with burstable 95th-percentile billing.
We've run BGP since our ISP days peering at the Seattle Internet Exchange. Routing decisions are ours to make, not something we resell.
Why Do Small Towns Welcome Depots?
A 1MW site with no new substation and no tax-break asks is a very different conversation than a hyperscale campus. We bring community contributions, training, and events. Towns get modern infrastructure and local jobs without straining the grid. IDACORE already hosts IdahoMesh MeshCore repeaters, and we'd rather be the neighbor people are glad to have.
What Should You Check Before You Ship Hardware?
A few things will save you a remote-hands bill:
- Airflow direction. Front-to-back only. Side-exhaust gear fights the cross-flow path.
- Cabinet depth. Depot cabinets are 48 inches deep. Confirm rail depth and cable clearance for deep GPU chassis.
- Power cords. PDUs are A+B with C13/C19 outlets. Match your PSU cords and split redundant PSUs across both feeds.
- Blanking panels. Fill every empty U. Bypass air is wasted air at 50kW.
- Density planning. 50kW per rack fits three 8-GPU B200-class servers.
Once you're racked, you can power-cycle your own gear from the IDACORE portal. When you need hands, remote hands runs $150/hr during business hours in 15-minute increments, and $250/hr after hours with a 1-hour minimum.
Frequently Asked Questions
Can a 50kW GPU rack be cooled with air alone?
Yes, if the building is designed around the air path. A 50kW rack needs roughly 5,000 to 8,000 CFM depending on the server temperature rise. IDACORE Depot 01 in Northeast Washington delivers that with cross-flow free-air cooling: outside air through automated louvers and MERV 13 filtration, across the servers, and out the far side. A direct evaporative wet wall handles summer. There are no compressors or chillers. That's enough for three 8-GPU B200-class servers in one rack.
What PUE does an IDACORE Depot run at?
The Depot design target is a PUE of about 1.1 to 1.2. That comes from removing compressors and chillers entirely. Heat rejection is outside air plus a direct evaporative wet wall, controlled by automated louvers and recirculation. For comparison, older compressor-cooled rooms commonly run around 1.5. At IDACORE Depots, power is billed at cost as metered IT load multiplied by PUE at the utility rate, with no markup, so the efficiency savings go straight to the customer.
How much does GPU colocation cost at IDACORE Depots?
IDACORE Depots are priced at $175/kW/month NNN on a 36-month term. That covers space, cooling, and facility infrastructure. Power bills on top at cost: metered IT load multiplied by PUE at the utility rate, with no markup. The 12- and 24-month terms carry a higher rate. There's no minimum deployment size. The deposit and first month are due at signing. Backup power, IP transit, transport, and remote hands are billed separately.
Do IDACORE Depots have backup power?
The base Depot offering is utility-fed with no UPS or generator. It's the lowest-cost tier and fits workloads that handle failure in software, like most inference fleets. If you need more, UPS plus generator or battery energy storage (BESS) is available as an add-on. You can also spread capacity across multiple Depots for site-level redundancy. Pick the resilience your workload needs instead of paying for gold-plating it doesn't use.
How fast can I get GPU racks powered in Northeast Washington?
IDACORE Depot 01 in Northeast Washington is live and energized now. Racks are powered in under two weeks from signing, with air-cooled capacity up to 50kW per rack and a 99.9% uptime SLA. IP transit from IDACORE's own AS36824 is delivered on-site, with Lumen and Cogent upstreams and 1G, 10G, or 100G handoffs. Check idacore.com/depots for current availability before you plan a delivery date.
If you're planning a dense GPU deployment and tired of paying for someone else's chiller plant, Depot 01 is energized now. It offers up to 50kW per air-cooled rack, power passed through at cost with no markup, and racks live in under two weeks. Check current availability at idacore.com/depots, then talk to us about a 50kW GPU rack at Depot 01. You'll get an engineer who can walk through your airflow and power plan, not a sales script.